7.4 JBUS table
7.4.1 Data for Pulsar 700 / 1000 / 1500
7.4.1.1 Status table
Status description Status to 0 Status to 1 Word (hex) Bit
Load protected no yes 40 0
UPS coupled no yes 40 1
Unit general alarm no yes 40 2
UPS in backup no yes 40 4
Battery low warning no yes 40 5
Low battery no yes 40 6
Operation on static switch no yes 40 7
Communication fault absent present 40 9
UPS overload no yes 40 A
Emergency stop absent present 40 B
Battery to be checked no yes 40 D
Device ventilation fault no yes 40 E
Battery present absent present 42 0
Mains 1 voltage out of tolerance no yes 44 8
Mains 1 frequency out of tolerance no yes 44 B
Bypass status no yes 46 7
Charger general fault no yes 49 0
Battery charge
not in
charge
in charge 49 1 & 3
Converter fault no yes 4A 1
Inverter fault no yes 4C 1