Network Management Card
– User Manual 34003991EN/EC Page 115/118
8.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11)
SNMP traps are sent when alarms appears and desappears.
Level : 1:informational , 2:major, 3:critical
MIB TRAP Trap # Level
-upsmgBatteryFault Trap 1 Level 3
-upsmgBatteryOK Trap 2 Level 1
-upsmgAtLowBattery Trap 5 Level 3
-upsmgFromLowBattery Trap 6 Level 1
-upsmgChargerFault Trap 7 Level 3
-upsmgChargerOK Trap 8 Level 1
-upsmgOnBattery Trap 11 Level 2
-upsmgReturnFromBattery Trap 12 Level 1
-upsmgOnByPass Trap 13 Level 2
-upsmgReturnFromByPass Trap 14 Level 1
-upsmgUtilityFailure Trap 17 Level 2
-upsmgUtilityRestored Trap 18 Level 1
-upsmgOverLoad Trap 21 Level 3
-upsmgLoadOK Trap 22 Level 1
-upsmgOverTemperature Trap 23 Level 3
-upsmgTemperatureOK Trap 24 Level 1
-upsmgOffToStart Trap 29 Level 2
-upsmgOffInProgress Trap 31 Level 3
-upsmgCommunicationFailure Trap 37 Level 3
-upsmgCommunicationRestored Trap 38 Level 1
-upsmgRedundancyLost Trap 65 Level 2
-upsmgRedundancyOK Trap 66 Level 2
-upsmgProtectionLost Trap 67 Level 2
-upsmgProtectionOK Trap 68 Level 2
If the Environment Sensor is detected , the following information are managed.:
- upsEnvironmentComFailure Trap 53 Level 2
- upsEnvironmentComOK Trap 54 Level 2
- upsEnvironmentTemperatureLow Trap 55 Level 2
- upsEnvironmentTemperatureHigh Trap 56 Level 2
- upsEnvironmentTemperatureOK Trap 57 Level 2
- upsEnvironmentHumidityLow Trap 58 Level 2
- upsEnvironmentHumidityHigh Trap 59 Level 2
- upsEnvironmentHumidityOK Trap 60 Level 2
- upsEnvironmentInput1Closed Trap 61 Level 2